Operating the thermostat on the device
Advanced settings
6
A6V10877569_en--_e 33 | 59
No.
Application
settings
Descriptions
Factory
settings
Range Dependencies
29. Humidify
(no fan)
min. ON
time
The minimum working
time of a standalone
humidifier. This
minimum limitation
protects the humidifier
from being destroyed
by frequent
switchovers.
3 min 0…60 min You’ve
configured the
thermostat
output as
“Humidifier (no
fan)” in
Changing
system setup
[ 36].
30. Humidify
(no fan)
min. OFF
time
The minimum OFF
time of a standalone
humidifier. This
minimum limitation
protects the humidifier
from being destroyed
by frequent
switchovers.
3 min 0…60 min
31. Dehum. (no
fan) min.
ON time
The minimum working
time of a standalone
dehumidifier. This
minimum limitation
protects the
dehumidifier from
being destroyed by
frequent switchovers.
3 min 0…60 min You’ve
configured the
thermostat
output as
“Dehumidifier
(no fan)” in
Changing
system setup
[ 36].
32.
Dehum. (no
fan) min.
OFF time
The minimum OFF
time of a standalone
dehumidifier. This
minimum limitation
protects the
dehumidifier from
being destroyed by
frequent switchovers.
3 min 0…60 min
33. DHW min.
ON time
The minimum working
time of the domestic
hot water boiler. This
minimum limitation
protects the boiler
from being destroyed
by frequent
switchovers.
3 min 0…60 min You’ve
configured the
thermostat
output as
“Domestic hot
water boiler” in
Changing
system setup
[ 36].
34. DHW min.
OFF time
The minimum OFF
time of the domestic
hot water boiler. This
minimum limitation
protects the boiler
from being destroyed
by frequent
switchovers.
3 min 0…60 min
Minimum switchover
time adjustment