Connecting
4.3 Loop-through connection of PROFINET IO and supply voltage
RF180C communication module
Operating Instructions, 12/2012, J31069-D0177-U001-A6-7618
27
NOTICE
Ensuring the degree of protection
The IP65, IP66 or IP67 degree of protection is no longer guaranteed when the connection
block is dismounted.
Notes for wiring
If you are wiring your structure, then you must take into account the impact of cable
length on supply voltage to the RF180C.
Example:
When using a 10 m long cable with a diameter of 1.5 mm
2
, the voltage drop is 2.5 V with
a loading of 10 A. This corresponds to 0.25 V at a 1 A load.
The maximum infeed current for connection block M12, 7/8" is 6 A at 1L+ and 8 A at 2L+.
These values must not be exceeded.
The maximum infeed current of the push-pull connection block is 12 A for 1L+ and 2L+ at
up to 40 °C and 8 A for 1L+ and 2L+ at up to 60 °C. These values must not be exceeded.
Adhere to the current carrying capacity of the connected cables, which depends on the
conductor material, the conductor cross-section and the ambient temperature.
NOTICE
Damage to the device
If you do not observe the maximum infeed current and the cable cross-section required,
this may result in the cable isolation and contacts overheating and to the device being
damaged.
NOTICE
Damage to the device
A cable cross-section of 2.5 mm² is mandatory for an amperage > 8 A!