Parameterization
5.4 Input parameters for RF180C
RF180C communication module
Operating Instructions, 12/2012, J31069-D0177-U001-A6-7618
37
5.4 Input parameters for RF180C
Input parameters for RF180C with FB 45
Assignment is made in UDT 10.
Table 5- 2 Input parameters for RF180C with FB 45
Address Name Permissible values Comment
+0.0 ASM_address 256, 260, 264, 268, ... Each RF180C occupies four bytes of I/O in
the I/O area of the controller
+2.0 ASM_channel 1, 2
+8.0 MDS_control B#16#0, 1 0 = no presence check
1 = presence check
+9.0 ECC_mode TRUE, FALSE
+9.1 RESET_long TRUE, FALSE TRUE,
if MOBY_mode = 5 (MOBY U/D; RF200 / RF300)
+10.0 MOBY_mode B#16#1, 4, 5, 6, 7, 8,
9, A, B
Special features of the MOBY I dialog (8):
Write/read device must be type SLG4x.
The VMDS memory size is 16KB. The INIT
command for the VMDS must be specified
using 4000 hex.
MOBY I:
B#16#00 ... FF
+11.0 scanning_time
MOBY U:
B#16#00 ... C8
A value not equal to 00 is only practical
if parameters for MOBY_mode have been set
accordingly.
MOBY D, RF300 reserved (00)
+12.0 option_1 B#16#00, 02, 04
MOBY U (normal output
power):
B#16#05, 0A, 0F, 14,
19, 1E, 23
MOBY U (reduced output
power):
B#16#85, 8A, 8F, 94,
99, 9E, A3
+13.0 distance_limiting
MOBY D:
B#16#02 ... 28
MOBY U/D
RF200, RF300 reserved (00)
+14.0 multitag B#16#1 MOBY U/D, RF200, RF300
MOBY U:
B#16#0, 1, 2, 3
+15.0 field_ON_control
MOBY D, RF300:
B#16#0
MOBY U/D, RF200, RF300
MOBY U:
B#16#00 ... FF
+16.0 field_ON_time
MOBY D:
B#16#00, 01
MOBY U/D
RF200, RF300 reserved (00)
Special information on the input parameters for RF180C with FB45 in conjunction with the
readers RF620R/RF630R can be found in the "Configuration manual RF620R/RF630R
(http://support.automation.siemens.
com/WW/view/en/33287195)".

Related product manuals