EasyManuals Logo

Siemens RUGGEDCOM RSG2488 Installation Manual

Siemens RUGGEDCOM RSG2488
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
Installing the Device
2.5.3Grounding the Device
1. Connect the positive wire from the power source to the positive terminal on the
terminal block.
2
4
1
6
3
5
4
5
6
3 7
7
7
7
1
Screw-Type Terminal Block for 24 and 48 Power Supply
2
Pluggable Terminal Block for 24P and 48P Power Supply
3
Positive Terminal for PS1
4
Negative Terminal for PS1
5
Positive Terminal for PS2
6
Negative Terminal for PS2
7
Chassis Ground
Figure2.7 DC Terminal Block Wiring
2. Connect the negative wire from the power source to the negative terminal on
the terminal block.
3. Connect the ground terminal on the power source to the ground terminal on the
device. For more information, refer to "Grounding the Device (Page 16)".
2.5.3 Grounding the Device
The RUGGEDCOM RSG2488 chassis ground terminal uses an M3 screw. It is
recommended to terminate the ground connection with an M3 ring or spade lug and
torque it to 1.7 N·m (15 lbf-in).
3
1
2
1
M3 Screw
2
Standoff
16
RUGGEDCOM RSG2488
Installation Manual, 07/2021, C79000-G8976-1048-11

Other manuals for Siemens RUGGEDCOM RSG2488

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RUGGEDCOM RSG2488 and is the answer not in the manual?

Siemens RUGGEDCOM RSG2488 Specifications

General IconGeneral
BrandSiemens
ModelRUGGEDCOM RSG2488
CategorySwitch
LanguageEnglish

Related product manuals