Condenser pump
Line no. Operating line
2800 Frost protection cond pump
Off.
On.
2801 Control cond pump
2802 Prerun time cond pump
2803 Overrun time cond pump
It can be defined whether or not the condenser pump shall be put into operation when
frost protection for the plant is activated.
Frost protection:condenser
pump
Off
The condenser pump does not run when frost protection for the plant is activated.
On
The condenser pump runs when frost protection for the plant is activated.
This defines whether the pump shall run when there is a valid request or only when the
compressor is in operation.
Control cond
pump
Temperature request
The condenser pump starts running as soon as there is a valid temperature request.
Parallel compressor operation
The condenser pump runs when at least one compressor is in operation.
The condenser pump also runs when the electric immersion heater installed in the flow
is in operation.
In the case of an active separate DHW circuit and DHW controlling element Q3 =
charging pump (5731), the condenser pump does not operate.
The condenser pump can also be activated by the following functions:
Frost protection for the plant
Frost protection for the heat pump
Storage tank recooling
Passive cooling
Prior to starting the compressor, the condenser pump must be activated, enabling the
sensors to acquire the correct temperature.
Prerun time cond pump
When the compressor is switched off, the condenser pump continues to run for the set
overrun time.
Overrun time cond pump
In the event of a heat pump fault, the cond
enser pump is deactivated until the fault is
corrected.
However, if activated, frost protection for the plant, the heat pump or the electric
immersion heater K25/K26 can still put the condenser pump into operation.
114/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 6 The settings in detail 28. September 2009