Device data
Line no. Operating line
70 Software version
The display shows the current version of the room unit..
6.3 Radio links
Binding
Line no. Operating line
120 Binding
No
Yes
121 Test mode
Off.
On.
For more detailed information, refer to the descriptions of the wireless components in
section 3.8.
When commis
sioning the system, the wireless peripheral devices (room unit) are
assigned to the basic unit.
Binding
The test mode is used for checking the radio link. The test should be made when the
installation is entirely completed.
Test mode
List of RF devices
Line no. Operating line
130 Room unit 1
Missing
Ready
No recept’n
Change batt
131 Room unit 2
Same as on operating line 130
132 Room unit P
Same as on operating line 130
133 Outside sensor
Same as on operating line 130
134 Repeater
Same as on operating line 130
135 Operator unit P
Same as on operating line 130
136 Operator unit P
Same as on operating line 130
137 Operator unit P
Same as on operating line 130
138 Operator unit 1
Same as on operating line 130
140 Delete all devices
The radio link to all devices will be cancelled. If radio communication is required again,
a new binding must be made.
Delete all devices
83/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 6 The settings in detail 28. September 2009