3-phase current
For monitoring the 3-phase current, the 3 phases must be connected to inputs Ex5, Ex6
and Ex7 in the correct order (L1, L2, and L3). The controller monitors the correct
temporal order of the 3 phases. Any phase asymmetry, phase interruption or too low
rated voltage of one or several phases is regarded as a 3-phase error.
If a 3-phase error is continuously present during the period of time set under "Delay 3-
phase error" (2894), the compressor is switched off for the minimum off time. The
controller delivers status message
180: Current asymmetrical.
If the 3-phase error occurs again within "Duration error repetition" (2889) for at least the
delay time, the heat pump initiates lockout, if the preselected number of errors has
been exceeded. The controller delivers error message
355: Current asymmetrical.
The heat pump must be manually reset.
Only RVS41..
Low-pressure switch E9
Input of a low-pressure switch (AC 230 V) upstream of the compressor.
High-pressure switch E10
Input of a high-pressure switch (AC 230 V) downstream from the compressor.
Overload compressor 1 E11
Input of an overload protection signal (AC 230 V) to compressor 1.
Error/alarm message
Input of an external error / alarm signal (AC 230 V).
Mixing group
Only RVS61..
Line no. Operating line
6014 Function mixing group 1
None
Heating circuit 1
Cooling circuit 1
Heating/cooling circuit 1
Primary controller / system pump
DHW primary controller
Instantaneous DHW heater
Defines use of mixing group 1 and of its inputs and outputs.
Function mixin
g group 1
The settings are made on the respective
menu page (heating circuit 1, cooling circuit 1,
etc.). Use the table below for the logical assignment of the sensors / relays of the
mixing group function to the physical terminals of the mixing group:
Logical assignment of sensors and relays per
mixing group function
Physical terminal on
the mixing group
Designation of