Sensors
Line no. Operating line
6200 Save sensors
At midnight, the basic unit saves the states at the sensor terminals, provided the
controller has previously been in operation for at least 2 hours.
If, after storage, a sensor fails, the basic unit generates an error message.
This setting is used to ensure immediate saving of the sensors. This is necessary
when, for instance, a sensor is removed because it is no longer needed.
Line no. Operating line
6201 Reset sensors
This setting is used to reset all connected sensors. The sensors are read in again using
function "Save sensors" (6200), or automatically at midnight, provided the controller
has previously been in operation for at least 2 hours.
Parameters
Line no. Operating line
6204 Save parameters
The current parameter settings can be saved as new default settings. Exempted from
this are the following menus: Time of day and date, operator section, wireless, and all
time programs, as well as the number of operating hours and the different meters.
Important:
With this proc
ess, the factory settings will be overwritten and cannot be retrieved!
Line no. Operating line
6205 Reset to default parameters
The parameters can be reset to their default values. Exempted from this are the
following menus: "Time of day and date", Operator section", "RF", and all time
programs, as well as the number of operating hours and the different counters.
Plant diagram
Line no. Operating line
6212 Check no. heat source 1
Solar
XX
6213 Check no. heat source 2
Heat pump
XX
6215 Check-No. storage tank
combi storage tank Buffer storage tank DHW storage tank
XX XX XX
6217 Check no. heating circuit
Heating circuit P Heating circuit 2 Heating circuit 1
XX XX XX
195/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 6 The settings in detail 28. September 2009