Defrost mode (air heat pumps)
Defrost mode is considered:
- If the internal defrost function is active.
In defrost mode:
- Energy acquisition is counted as employed energy heating
- Energy supply is not counted
Line no. Operating line
3190
Reset fixed day storage
Reset fixed day storage
The parameter
Reset fixed day storage deletes the entire storage with all entries.
All entries or their values are displayed with "---".
6.14 Cascade
Control
Line no. Operating line
3530 Release integral source seq
3531 Reset integral source seq
3533 Switch-on delay
When, with the heat source currently in operation, the demand for heat cannot be met -
the difference being the release integral set here - another heat source is switched on.
Release integr
al source
seq
When the valu
e is increased, additional heat sources are switched on at a slower rate.
When the value is decreased, the heat sources are switched off at a faster rate.
When, with the heat source currently in operation, the demand for heat is exceeded by
the reset integral set here, the heat source with the highest priority is shut down.
Reset integral
heat
source seq
When the valu
e is increased, the heat sources operate for longer periods of time (in the
case of excess heat).
When the value is decreased, the heat sources are switched off at a faster rate.
Sw
itch-on delay
Correct setting of the s
witch-on delay ensures that the plant maintains stable operating
states. This prevents frequent cycling of the heat sources.
With DHW requests, the delay time is fixed at one minute.
Heat source sequence
Line no. Operating line
3540 Auto source seq ch’over
3541 Auto source seq exclusion
None
First
Last
First and last
@
With automatic source sequence changeover, the heat source loads in a cascade can
be influenced by defining the order of lead and lag heat source.
uto source seq ch’over
Fixed order
Setting - - - defines a fixed order.
The heat sources are switched on and off in the order of their LPB device addresses.
Order according to the number of operating hours
148/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02