Operator unit / service unit
The operator unit supports the heating circuits activated in the basic unit.
When using th
is setting, the operator unit does not acquire and deliver the room
temperature.
Heating circuit assignment
Line no. Operating line
42 Assignment device 1
Heating circuit 1
Heating circuits 1 and 2
Heating circuits 1 and P
All heating circuits
44 Operation HC2
Commonly with HC1
Independently
46 Operation HCP
Commonly with HC1
Independently
48 Action occupancy button
None
Heating circuit 1
Heating circuit 2
Jointly
As device 1 (setting 40), the action of the relevant operator section on heating circuit 1
or on both heating circuits can be assigned. The latter is required especially when using
2 heating circuits and only 1 room unit.
ssignment device 1
Depending on
operating line 40, the action of operation (operating mode button or
setting knob) on room unit 1, on the operator unit or service unit can be defined for
heating circuit 2.
Operation HC2
Commonly with HC1
Operation acts commonly on heating circuits 1 and 2.
Independently
The action of operation is queried on the display as soon as the operating mode button
is pressed or the setting knob is operated.
Depending on operating line 40, the action of operation (operating mode button or
setting knob) on room unit 1, on the operator unit or service unit can be defined for
heating circuit P.
Operation HCP
Commonly with HC1
Operation acts commonly on heating circuits 1 and 2.
Independently
Operating mode changes or readjustments of the Comfort setpoints are to be made in
programming mode.
The action of the occupancy button on the operator unit can be assigned to the relevant
heating circuits.
ction occupancy button
If only one he
ating circuit is assigned, the occupancy button always acts on that heating
circuit.
Room sensor
Line no. Operating line
54 Readjustment room sensor
The temperature display can be readjusted.
82/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 6 The settings in detail 28. September 2009