Bus power
supply
:function
The bus power supply enables the bus system to be powered directly by the individual
controllers (no central bus p
ower supply). The type of bus power supply can be
selected.
Off: No bus power supply via the controller
Automatically: The bus power supply (LPB) via the controller is automatically
switched on and off depending on the requirements of the LPB
Bus po
wer supply state
The display sh
ows whether the controller currently supplies power to the bus:
Off: Bus power supply via the controller is currently inactive
On: The bus power supply via controller is currently active. At the moment, the
controller supplies some of the power required by the bus
Central functions
Line no. Operating line
6620 Action changeover functions
Segment
System
6621 Summer changeover
Locally
Centrally
6623 Optg mode changeover
Locally
Centrally
6625 DHW assignment
Local HCs
All heating circuits in the segment:
All HCs in system
6627 Refrigeration request
Locally
Centrally
6632 Bit Eco from ext source
No
Yes
These setting
s are only relevant for device address 1.
The range of action of central changeover can be defined.
A
ction changeover
functions
This concerns
:
Operating mode changeover via H input (for setting "central" in setting lines 6623)
Summer changeover (when selecting "Central" on operating line 6621)
The possible settings are the following:
Segment: Changeover takes place with all controllers in the same segment
System: With all controllers, changeover takes place in the entire system (in all
segments). For that, the controller must be located in segment 0!
The range of action of summer changeover is as follows:
Summer chan
geover
Local entry:
Local action; the local heating circuit is switched on the basis of operating lines 730,
1030 and 1330
Central entry: Central action; depending on the setting made on operating line
"Action changeover functions", either the heating circuits in the segment or those of
the entire system are switched based on operating line 730.
199/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 6 The settings in detail 28. September 2009