Operating
line
Operating
level
Function
Default value
Min
Max
Unit
Off ¦ On
2951 I Defrost release below OT 7 5 20 °C
2958 I Numb defrost attempts max 3 0 10 -
2962 I Duration defrost lock 30 0 100 min
2963 I Time up to forced defrost 120 60 600 min
2964 I Defrost time max 10 1 42 min
2965 I Dripping time evapor 2 0 10 min
3000 I Switch-off temp max cooling 40 20 60 °C
3002 F Source temp min cool mode 2 -20 30 °C
3004 F SD ch’over cooling pas/act 5 1 10 °C
3006 F During compressor operation
Passive cooling off ¦ Passive cooling on
Passive cooling on 1 -
3007 F In passive cooling mode
Condenser pump off ¦ Condenser pump on
Condenser pump off 1 -
3008 F Temp diff cond cooling mode 5 0 20 °C
3030 F Auto readj HP cond sensor
Off ¦ Now ¦ After pump prerun
Off. -
3031 F Readj HP flow sensor 0 -20 20 °C
3032 F Readj HP return sensor 0 -20 20 °C
3033 F Readj status
Not readjusted ¦ Manually readjusted ¦ Automatically
readjusted ¦ Readjustment running
Energy meter
3090 F Pulse count heat
None With ¦ Input H1 ¦ With input H3
None -
3092 F Pulse unit heat
None ¦ kWh ¦ Liter
None
3093 F Pulse unit heat numer 1 1 1000 -
3094 F Pulse unit heat denom 1 1 1000
3097 F Flow heating --- 10 60000 l/h
3098 F Flow DHW --- 10 60000 l/h
3100 F Pulse count energy
None With ¦ Input H1 ¦ With input H3
None
3102 F Pulse unit energy
None ¦ kWh ¦ m3
None
3103 F1 Pulse value energy numer 1 1 1000
3104 F1 Pulse value energy denom 1 1 1000
3106 F2 Mean gas energy content 11.5 1 100 kWh/m3
3108 F1 Electric source output --- 0.1 10 kW
3110 F2 Heat delivered 0 0 9999999 kWh
3113 F2 Energy brought in 0 0 3500000 kWh
3116 F2 Performance factor --- 0 10
3119 F1 Fixed day yearly perf factor 30.6. 1.01 31.12 dd.MM
3120 E Yearly perf factor 1 --- 0 10
3120 E Fixed day 1 1.9.2004 31.12.2099 dd.MM.y
yyy
3121 E Heat delivered heating 1 0 0 9999999 kWh
3122 E Heat delivered DHW 1 0 0 9999999 kWh
3124 E Energy brought in heating 1 0 0 3500000 kWh
3125 E Energy brought in DHW 1 0 0 3500000 kWh
3127 E Yearly perf factor 2 --- 0 10