Line no. Operating line
7700 Relay test
Only RVS61.. Only RVS41..
No test
Everything off
Source pump Q8 / fan K19
Compressor K1 (for approx. 1
– 2 s.)
Condenser pump Q9
DHW pump Q3
Heating circuit pump 1
Heating circ mix valve op Y1
Heat circ mix valve cl Y2
Relay output QX23 module 1
Relay output QX21 module 1
Relay output QX22 module 1
Relay output QX1
Relay output QX2
Relay output QX3
Relay output QX4
Relay output QX5
Relay output QX6
Relay output QX23 module 2
Relay output QX21 module 2
Relay output QX22 module 2
No test
Everything off
Relay output QX23 module 1
Relay output QX21 module 1
Relay output QX22 module 1
Relay output QX1
Relay output QX2
Relay output QX3
Relay output QX4
Relay output QX5
Relay output QX6
Relay output QX23 module 2
Relay output QX21 module 2
Relay output QX22 module 2
Relay output QX7
Relay output QX8
Important:
During the relay test, limitations are not active.
Only RVS41..
When usi
ng a multifunctional output for compressor K1, the output will be disabled
for about 1 to 2 seconds.
Output test UX
By selecting a setting from output test UX / P1, an appropriate signal is delivered,
enabling it to be checked.
Line no. Operating line
7710 Output test UX
7711 Voltage signal UX
7714 PWM signal P1
Input test sensors
By selecting a setting from input test sensors, the relevant input is displayed, enabling it
to be checked.
Line no. Operating line
7730 Outside temp B9
7732 Flow temp B1
7750 DHW temp B3
7770 Flow temp HP B21
7771 Return temp HP B71
7772 Hot-gas temp B81
7775 Source inlet temp B91
7777 Sensor temp B92, B84
7820 Sensor temp BX1
7821 Sensor temp BX2
7822 Sensor temp BX3
7823 Sensor temp BX4
7824 Sensor temp BX 5
7830 Sensor temp BX21 module 1
7831 Sensor temp BX22 module 1
7832 Sensor temp BX21 module 2
7833 Sensor temp BX22 module 2
Only RVS61..
Only RVS61..
The selected sensor values are updated within a maximum of 5 seconds.
The display is made with no measured value correction.
211/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 6 The settings in detail 28. September 2009