Types of sensor / readjustment
Line no. Operating line
6097 Sensor type collector
NTC
Pt 1000
6098 Readjustm collector sensor
6099 Readjustm coll sensor 2
6100 Readjustm outside sensor
Only RVS61..
Sensor type c
ollector Selection of ty
pe of sensor used. The controller uses the respective temperature
characteristic.
Sensor readju
stments The measured value of the respective sen
sors can be readjusted by +/- 3 K.
Building and room model
Line no. Operating line
6110 Time constant building
When the outside temperature varies, the room temperature changes at different rates,
depending on the building's thermal storage capacity (type of building construction).
The above setting is used to adjust the response of the flow temperature setpoint to
varying outside temperatures.
• Example:
> 20
The room temperature will respond more slowly to outside temperature variations.
10 - 20
This setting can be used for most types of buildings.
< 10
The room temperature will respond more quickly to outside temperature variations.
Setting 0: Function switched off. The attenuated as well as mixed temperature are the
same as the present outside air temperature.
193/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 6 The settings in detail 28. September 2009