BSB
Max. cable length basic unit
peripheral device
Max. total length
Min. cross-sectional area
2-wire connection, not interchangeable
200 m
400 m (max. cable capacitance) 60 nF)
0.5 mm
2
LPB
With bus power supply via controller
(per controller)
With central bus power supply
Bus loading number
(copper cable 1.5 mm
2
, 2-wire not
interchangeable)
250 m
460 m
E = 3
Interfaces
Degree of protection of housing to
EN 60 529
IP 00
Safety class to EN 60 730 low-voltage-carrying parts meet the
requirements of safety class II, if correctly
installed
Degree of pollution to EN 60 730 normal pollution
Degr
ee of protection and
safety class
CE conformity to
EMC directive
- Immunity
- Emissions
Low-voltage directive
Electrical safety
2004/108/EC
- EN 61000-6-2
- EN 61000-6-3
2006/95/EC
- EN 60730-1, EN 60730-2-9
Standards, safet
y, EMC,
etc.
Storage to EN 60721-3-1 class 1K3, temp. -20…65 °C
Transport to EN 60721-3-2 class 2K3, temp. -25…70°C
Operation to EN 60721-3-3 class 3K5, temp. -20...50°C (non-condensing)
Climatic conditions
Without packaging RVS61.843: 607 g
RVS41.813 420 g
Weight
8.2 Extension module AVS75.390
Rated voltage AC 230 V (+10% / -15%)
Bemessungsfrequenz 50/60 Hz
Power consumption max. 4 VA
Fusing of supply lines Automatic cutout: Max. 13 A to EN 60898-1
Fuse: Max. 10 AT
Po
wer supply
(Power supply and outputs) solid wire or stranded wire (twisted or with
ferrule):
1 core: 0.5...2.5 mm
2
2 cores 0.5...1.5 mm
2
Wir
ing of terminals
Software class A
Mode of operation to EN 60 730 1b (automatic operation)
Functio
nal data
Digital inputs H2 safety extra low-voltage for potentialfree
low-voltage contacts:
voltage with contact open: DC 12 V
current with contact closed: DC 3 mA
Analog input H2 protective extra low-voltage operating
range: DC (0...10) V
internal resistance: > 100 k
Mains input L AC 230 V (± 10 %)
internal resistance: > 100 k
Sensor inputs BX6, BX7 NTC 10k (QAZ36, QAD36)