If the value lies above setting "Max starts compr1/hrs run" (7072), symbol appears
on the display and a maintenance message on the info level:
8: Too many starts compr 1 (priority 9)
This parameter can be reset, provided the respective access right is granted.
Reset
Maximum number of starts of compressor 2 per hour run
Setting the maximum permissible number of starts of compressor 2 per hour run.
Max
starts compr2/hrs run
Average num
ber of starts of compressor 2 per hour run, reached over the last 6 weeks. Curr starts comp2/hrs run
If the value is above setting "Max starts compr2/hrs run" (7074), symbol
appears on
the display and a maintenance message on the info level:
9: Too many starts compr 2 (priority 9)
Reset
This parameter can be reset, provided the respective access right is granted.
Number of times per week the temperature differential across the condenser
exceeds the maximum
Setting the number of times within a 7-day period the maximum temperature differential
across the condenser may be exceeded.
Diff condens
max/week
Number of times the maximum temperature differential across the co
ndenser was
exceeded within a 7-day period. If the value is above setting "Diff condens max/week"
(7076), symbol
appears on the display and a maintenance message on the info
level:
13: Diff condens max (priority 3)
Cur diff conde
ns
max/week
This parameter can be reset, provided the respective acc
ess right is granted.
Reset
Number of times per week the temperature differential across the condenser falls
below the minimum
Diff condens
min/week
Indicates how many times the temperature differential across the condenser may drop
belo
w the minimum within a 7-day period.
Number of times the temperature differential across the condenser dropped below the
minimum within a 7-day period. If the value is above setting "Diff condens min/week"
(7078), symbol
appears on the display and a maintenance message on the info
level:
14: Diff condens min (priority 3)
Cur diff conde
ns
min/week
This parameter can be reset, provided the respective acc
ess right is granted.
Reset
Number of times per week the temperature differential across the evaporator
exceeds the maximum
Indicates how many times within a 7-day period, the maximum temperature differential
across the evaporator may be exceeded.
Diff evap ma
x/week
Number of times the maximum temperature differential across the ev
aporator was
exceeded within a 7-day period. If the value lies above setting "Diff evap max/week"
(operating line 7080), symbol
appears on the display and the info level shows the
following maintenance message:
15: Diff evap max (priority 3)
Cur diff evap max/week
Reset
This parameter can be reset, provided the respective access right is granted.
207/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 6 The settings in detail 28. September 2009