Operating
line
Operating
level
Function
Default value
Min
Max
Unit
562 E 1. Phase off 05:00 00:00 24:00 hh:mm
563 E 2. Phase on 24:00 00:00 24:00 hh:mm
564 E 2. Phase off 24:00 00:00 24:00 hh:mm
565 E 3. Phase on 24:00 00:00 24:00 hh:mm
566 E 3. Phase off 24:00 00:00 24:00 hh:mm
576 E Default values
No ¦ Yes
No 1 -
Time program 5 / DHW
600 E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
Mo - Su -
601 E 1. Phase on 06:00 00:00 24:00 hh:mm
602 E 1. Phase off 22:00 00:00 24:00 hh:mm
603 E 2. Phase on 24:00 00:00 24:00 hh:mm
604 E 2. Phase off 24:00 00:00 24:00 hh:mm
605 E 3. Phase on 24:00 00:00 24:00 hh:mm
606 E 3. Phase off 24:00 00:00 24:00 hh:mm
616 E Default values
No ¦ Yes
No -
Holidays heating circuit 1
642 E Start --.-- 01.01 31.12 dd.MM
643 E End --.-- 01.01 31.12 dd.MM
648 E Operating level
Frost protection ¦ Reduced
Frost protection -
Holidays heating circuit 2
652 E Start --.-- 01.01 31.12 dd.MM
653 E End --.-- 01.01 31.12 dd.MM
658 E Operating level
Frost protection ¦ Reduced
Frost protection -
Holidays heating circuit P
662 E Start --.-- 01.01 31.12 dd.MM
663 E End --.-- 01.01 31.12 dd.MM
668 E Operating level
Frost protection ¦ Reduced
Frost protection -
Heating circuit 1
710 E Comfort cooling setpoint 20.0 Operating line 712 Operating line 716 °C
712 E Reduced setpoint 19 Operating line 714 Operating line 710 °C
714 E Frost protection setpoint 10.0 4 Operating line 712 °C
716 F Comfort setpoint max 35.0 Operating line 710 35 °C
720 E Heating curve slope 0.8 0.10 4.00 -
721 F Heating curve displacement 0.0 -4.5 4.5 °C
726 F Heating curve adaption
Off ¦ On
Off. -
730 E Summer/winter heating limit 18 / 8 30 °C
732 F 24-hour heating limit -3 / -10 10 °C
740 I Flow temp setpoint min 8 8 Operating line 741 °C
741 I Flow temp setpoint max 50 Operating line 740 95 °C
750 F Room influence 20 / 1 100 %
760 F Room temperature limitation 1 / 0.5 4 °C
770 F Boost heating / 0 20 °C
780 F Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint -
48/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 5 Handling 28. September 2009