Operating
line
Operating
level
Function
Default value
Min
Max
Unit
2
5934 I Sensor input BX5
None ¦ Buffer sensor B4 ¦ Buffer sensor B41 ¦ Collector
sensor B6 ¦ DHW sensor B31 ¦ Hot-gas sensor B82 ¦
Refrig sensor liquid B83 ¦ DHW charging sensor B36 ¦
DHW outlet sensor B38 ¦ DHW circulation sensor B39 ¦
Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦
Solar flow sensor B63 ¦ Solar return sensor B64 ¦ Buffer
sensor B42 ¦ Common flow sensor B10 ¦ Cascade return
sensor B70 ¦ Special temp sensor 1 ¦ Special temp sensor
2
None -
5950 I Function input H1
Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦
Error/alarm message ¦ Min flow temp setpoint ¦ Heat
request 10V ¦ Dewpoint monitor ¦ Flow temp setp incr
hygro ¦ Refrigeration request ¦ Refrigeration request 10V ¦
Pressure measurement 10V ¦ Rel room humidity 10V ¦
Room temp 10V ¦ Release swimming pool ¦ Swi-on
command HP stage 1 ¦ Pulse count
Optg mode changeover
HCs+DHW
-
5950 I Function input H1
Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦
Error/alarm message ¦ Min flow temp setpoint ¦ Heat
request 10V ¦ Dewpoint monitor ¦ Flow temp setp incr
hygro ¦ Refrigeration request ¦ Refrigeration request 10V ¦
Pressure measurement 10V ¦ Rel room humidity 10V ¦
Room temp 10V ¦ Release swimming pool ¦ Swi-on
command HP stage 1 ¦ Swi-on command HP stage 2¦
Pulse count
Optg mode changeover
HCs+DHW
-
5951 I Contact type H1
NC ¦ NO*
-
5952 I Function value, contact type H1 30 0 130 °C
5953 I Voltage value 1 H1 0 0 10 V
5954 I Function value 1 H1 0 -100 500 -
5955 I Voltage value 2 H1 10 0 10 V
5956 I Function value 2 H1 100 -100 500 -
5960 I Function input H3
Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦
Error/alarm message ¦ Min flow temp setpoint ¦ Heat
request 10V ¦ Dewpoint monitor ¦ Flow temp setp incr
hygro ¦ Refrigeration request ¦ Refrigeration request 10V ¦
Pressure measurement 10V ¦ Rel room humidity 10V ¦
Room temp 10V ¦ Release swimming pool ¦ Swi-on
command HP stage 1 ¦ Pulse count
Optg mode changeover HCs+DHW -
5960 I Function input H3
Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦
Error/alarm message ¦ Min flow temp setpoint ¦ Heat
request 10V ¦ Dewpoint monitor ¦ Flow temp setp incr
hygro ¦ Refrigeration request ¦ Refrigeration request 10V ¦
Pressure measurement 10V ¦ Rel room humidity 10V ¦
Room temp 10V ¦ Release swimming pool ¦ Swi-on
command HP stage 1 ¦ Swi-on command HP stage 2¦
Pulse count
Optg mode changeover HCs+DHW -
5961 I Contact type H3
NC ¦ NO
NO -
5962 I Function value contact H3 30 0 130 °C
6)
4)
6)
4)
6)
63/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 5 Handling 28. September 2009