Operating
line
Operating
level
Function
Default value
Min
Max
Unit
6046 I Function input H2
None ¦ Optg mode change HCs+DHW ¦ Optg mode
changeover HCs ¦ Optg mode changeover HC1 ¦ Optg
mode changeover HC2 ¦ Optg mode changeover HCP ¦
Error/alarm message ¦ Min flow temp setpoint ¦ Heat
request 10V ¦ Dewpoint monitor ¦ Flow temp setp incr
hygro ¦ Refrigeration request ¦ Refrigeration request 10V ¦
Pressure measurement 10V ¦ Rel room humidity 10V ¦
Room temp 10V ¦ Release swimming pool ¦ Swi-on
command HP stage 1 ¦ Swi-on command HP stage 2
Optg mode changeover HCs+DHW -
6047 I Contact type H2
NC ¦ NO
NO -
6048 I Function value contact H2 30 0 130 °C
6049 I Voltage value 1 H2 0 0 10 V
6050 I Function value 1 H2 0 -100 500 -
6051 I Voltage value 2 H2 10 0 10 V
6052 I Function value 2 H2 100 -100 500 -
6070 I Function output UX
None ¦ Source pump Q8/fan K19 ¦ Collector pump Q5 ¦
Solar pump buffer K8 ¦ Solar pump ext exch K9
¦ Solar
pump swi pool K18
¦ HP setpoint ¦ Output request ¦ Heat
request ¦ Refrigeration request
None -
6070 I Function output UX
None ¦ Source pump Q8/fan K19 ¦ DHW pump Q3 ¦ DHW
intern circ pump Q33 ¦ Instant DHW heater Q34 ¦ Collector
pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump buffer K8 ¦
Solar pump ext exch K9 ¦ Solar pump swi pool K18 ¦ Heat
circ pump HC1 Q2 ¦ Heat circ pump HC2 Q6 ¦ Heat circ
pump HCP Q20 ¦ HP setpoint ¦ Output request ¦ Heat
request ¦ Refrigeration request
None -
6071 I Signal logic output UX
Standard ¦ Inverted
Standard -
6072 I Signal output UX
0..10V ¦ PWM
0..0.10V -
6075 I Temp value 10V UX 100 5 130 °C
6097 F Sensor type collector
NTC* ¦ Pt 1000
1 1 2 -
6098 F Readjustm collector sensor 0 -20 20 °C
6099 F Readjustm coll sensor 2 0 -20 20 °C
6100 F Readjustm outside sensor 0.0 -3.0 3.0 °C
6110 F Time constant building 20 0 50 h
6120 F Frost protection for the plant
Off ¦ On
On. -
6135 F Air dehumidifier
Off ¦ On
Off. -
6136 F Release air dehumidifier
24h/day ¦ Time progr HC ¦ Time program 5
24h / day -
6137 F
Air dehumidifier r.h. ON
55 0 100 %
6138 F Air dehumidifier r.h. SD 5 2 50 %
6200 F Save sensors
No ¦ Yes
No -
6201 F Reset sensors
No ¦ Yes
No -
6204 F Save parameters
No ¦ Yes
No -
6205 F Reset to default parameters
No ¦ Yes
No -
6212 I Check no. heat source 1 - 0 199999 -
6)
4)
6)
6)