94/258
Siemens Switzerland Ltd User manual RVS61.843, RVS41.813 CE1U2355en_02
HVAC Products 6 The settings in detail 28. September 2009
Line no. Operating line
HC1 HC2 HCP
850 1150 1450 Floor curing function
Off
Functional heating (Fh)
Curing heating (Bh)
Functional/curing heating
Curing heating/functional heating
Manually
851 1151 1451 Floor curing setpoint manually
1455 Floor curing setpoint current
1456 Floor curing day current
1457 Floor curing days complete
Off:
Function is deactivated.
Functional heating (Fh) :
The first part of the temperature profile is automatically completed.
Floor curing heating (Bh)
The second part of the temperature profile is handled automatically.
Floor curing heating and functional heating
The entire temperature profile (first and second part) is handled automatically.
Manually
It is not a temperature profile that is completed, but the floor setpoint is controlled
manually. The function is automatically ended after 25 days.
The flow temperature setpoint for the "manual" floor curing function can be set
separately for each heating circuit.
Shows the current flow temperature setpoint of the running floor curing process.
Shows the current day of the running floor curing process.
If the floor curing process is terminated, the days completed are saved and retained
until the function is started the next time.
After a power failure, the plant resumes the floor curing function at the point in time the
power failure occurred.
In automatic operating modes, the controller ensures automatic completion of the
selected temperature profile.
50
45
40
35
30
20
5101518[Tag