Micro Automation Set 14 Entry ID 21062588
V2.0 05/18/05 25/35
Copyright © Siemens AG 2005 All rights reserved
Set14_DocTech_V2.0_en.doc
9.
Ensure that the configuration PC is
connected to WinAC “Backup” via
SCALANCE X108. Load the program to
the WinAC station.
10.
Connect WinAC “Backup” to S7-200
“Basis” via SCALANCE X108.
11. Restart S7-200 “Basis”.
Configuring WinCC flexible “HMI” station
Table 5-8
No. Function Comment
1.
To ensure the functionality of Micro
Automation Set 14, the following software
must be installed:
WinCC flexible 2005 ES with 512
PowerTags Runtime license
2.
The following network settings have to be
applied on the used network card of
WinCC flexible “HMI”:
IP address: 192.168.2.142
Subnet mask: 255.255.255.0
3.
Select Programs/Settings/ “Set PG/PC
Interface” to set the access point of the
used Ethernet network card to
“S7ONLINE Æ TCP/IP(Auto) network
controller”.
Configuration PC
IE cable
SCALANCE X108
IE cable
WinAC
Backup”
IE cable
SCALANCE X108
IE cable
WinAC
Backup”
S7-200 Basis”