NOTICE
Suitable fuse for the power supply cables (corresponds to "Limited Energy")
The current on the terminal may not exceed 3 A. Use a fuse for the power supply that is suitable
for protection of AC/DC power supply circuits *
)
and protects against currents > 3 A.
In areas subject to the NEC or CEC, the fuse must meet the following requirements:
Suitable for AC/DC *
)
(min. 60 V / 3 A)
Breaking current at least 10 kA
Approval according to ANSI/UL 248-14 (suppl. fuses), ANSI/UL 248-4 (Class CC), ANSI/UL
248-8 (J), ANSI/UL 248-15 (T), or CSA C22.2-4 No. 248.14 (suppl. fuses), No. 248-4
(Class CC), No. 248-8 (J), No. 248-15 (T)
In other areas, the fuse must meet the following requirements:
Suitable for AC/DC *
)
(min. 60 V / 3 A)
Breaking current at least 10 kA
Approval according to IEC/EN 60947‑1/2/3 or IEC/EN 60898-1/2 for circuit breakers
Switch o󹪜 characteristics: B or C
Approval according to IEC/EN 60127-1 for fuses
Switch o󹪜 characteristics: max. 120 s at 2 x I
n
(corresponds to melting integral I
2
t < 4320)
If the properties of the supplying current source are known, the following fuse is also possible:
In areas subject to the NEC or CEC, the fuse must meet the following requirements:
Suitable for AC/DC *
)
(min. 60 V / 3 A)
Breaking current > highest possible current of the current source (incl. short circuit
current and fault)
Approval according to UL 1077 or CSA C22.2 No. 235
In other areas, the fuse must meet the following requirements:
Suitable for AC/DC *
)
(min. 60 V / 3 A)
Breaking current > highest possible current of the current source (incl. short circuit
current and fault)
Approval according to IEC/EN 60934
Switch o󹪜 characteristics: max. 120 s at 2 x I
n
You do not need to fuse the supply cable if you only use power sources with a limited power
source (LPS) or power sources according to NEC Class 2 or PS2/LPS according to UL 62368-1 for
the power supply of the devices.
*
)
AC or DC depending on availability
Connecting up
6.3 24 V AC/DC power supply
SCALANCE XRH-300/XRM-300
Equipment Manual, 10/2022, C79000-G8976-C546-01 57