EasyManua.ls Logo

Siemens SENTRON 3VL series - Page 144

Siemens SENTRON 3VL series
318 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
11.4 Derating factors
3VL IEC molded case circuit breakers
144 System Manual, 11/2013, 110 0110 - 02 DS 03
Plug-in or withdrawable version:
Table 11- 17 Derating factors thermal-magnetic overcurrent releases (plug-in or withdrawable version)
Molded
case circuit
breaker
Release
Thermal-magnetic TM
Coefficient
at
From [A]
To [A]
40 °C
50 °C
60 °C
70 °C
VL160X
16
40
1
1
1
1
VL160 &
VL160X
50
100
1
1
1
1
125
160
1
0,9
0,9
0,9
VL250
200
250
1
0,9
0,9
0,9
VL400
200
250
1
1
1
1
315
400
1
0,9
0,9
0,9
VL630
315
400
1
1
1
1
500
630
1
0,85
0,85
0,85
Example for VL250:
I
n
= 200 A at 50 °C
Ambient temperature = 60 °C
1. Fixed-mounted version:
I
n
= 200 x 0.93
1)
= 186 A
Set I
R
to the next lowest value -> I
R
= 0.9 = 180 A
2. Plug-in or withdrawable version:
I
n
= 200 x 0.93
1)
x 0.9
2)
= 167 A
-> Calculation of overall derating = 0.93 x 0.9 = 0.837
-> Set I
R
to the next lowest value -> I
R
= 0.8 = 160 A
1)
Derating factor from the table "Derating factors of thermal-magnetic overcurrent releases"
2)
Coefficient for plug-in or withdrawable version from the table "Derating factors for thermal-
magnetic overcurrent releases (plug-in or withdrawable version)"