Technical data
11.4 Derating factors
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
145
Thermal-magnetic overcurrent release + RCD module
Fixed mounting:
Table 11- 18 Derating factors for thermal-magnetic overcurrent release + RCD module (fixed
mounting)
Molded
case
circuit
breaker
I
n
At 50 °C
[A]
Cross-
section Cu
[mm
2
] min.
Cross-
section Al
[mm
2
] min.
Max. rated uninterrupted current according to the
ambient temperature x I
n
40 °C
50 °C
60 °C
70 °C
VL160X
16
2,5
4
1
1
0,93
0,8
20
2,5
4
1
1
0,93
0,8
25
4
6
1
1
0,93
0,8
32
6
10
1
1
0,93
0,8
40
10
10
1
1
0,93
0,8
50
10
16
1
1
0,93
0,8
63
16
25
1
1
0,93
0,8
80
25
35
1
1
0,93
0,8
100
35
50
1
1
0,93
0,8
120
50
70
1
1
0,93
0,8
160
70
95
1
1
0,93
0,8
VL160
50
10
16
1
1
0,93
0,8
63 16 25 1 1 0,93 0,8
80
25
35
1
1
0,93
0,8
100 35 50 1 1 0,93 0,8
125
50
70
1
1
0,93
0,8
160
70
95
1
1
0,93
0,8
VL250
200
95
120
1
1
0,86
0,8
250
120
185
1
1
0,86
0,8
VL400
200
95
120
1
1
0,86
0,8
250
120
185
1
1
0,86
0,8
315
185
2x120
1
1
0,86
0,8
400
240
2x150
1
1
0,86
0,8