Technical data
11.4 Derating factors
3VL IEC molded case circuit breakers
146 System Manual, 11/2013, 110 0110 - 02 DS 03
Plug-in or withdrawable version:
Table 11- 19 Derating factors for thermal-magnetic overcurrent release + RCD module (plug-in or
withdrawable version)
Molded
case circuit
breaker
Release
Thermal-magnetic TM
VL160 &
VL400
Electronic trip unit
Fixed mounting:
Table 11- 20 Derating factors for electronic trip unit (fixed mounting)
Molded
case
circuit
breaker
n
2
2
Max. rated uninterrupted current according to the
ambient temperature x I
n
VL160
VL250
VL400
VL1250 1000 600 -- 1 1 1 0,8
Note
The electronic trip units with order No. supplement (9th and 10th position) Sx, Mx, Lx, Tx, Nx
and Ux have a thermal self
-protection feature that trips the breaker if the electronics
°C.