Tripped signaling switch (TAS)
The tripped signaling switch (TAS) signals every type of tripping of the circuit breaker:
Tripping of the ETU due to overcurrent (overload, short-circuit, …)
Tripping of the ETU by the residual current module Rc
Tripping of the shunt or undervoltage release
Mechanical tripping by PUSH TO TRIP pushbutton
Mechanical tripped signal RESET button
The circuit breaker can only be reclosed once the mechanical signaling button for "ETU
tripped" (reset) has been operated or the circuit breaker has been reset to its normal
operating position manually or by means of the remote reset magnet RR.
The trip alarm switch (TAS) can only be used for 3VA27 molded case circuit breakers with
toggle.
Auxiliary switch AUX
The auxiliary contacts signal the current CLOSED or OPEN position of the circuit breaker.
The four internal auxiliary contacts AUX 4CO are installed in each circuit breaker and
non-automatic air circuit breaker as standard. The user can modify these for 24 V digital
signals or mixed contacts during device con󹪝guration as shown in the following table. An
additional external breaker position query is possible with an expansion by 15 external
auxiliary switches with AUX15CO. You will 󹪝nd the necessary modi󹪝cation of the circuit
breaker side wall in Chapter External accessories (Page112).
Accessories
3.2Electromechanical accessories
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
102 Equipment Manual, 10/2023, L1V30499596002-03