Operation
6
6.1 Operation
6.1.1 Opening and closing
Closing and opening manually
The air circuit breaker can be closed and opened manually with the pushbuttons on the front.
1
2
3
4
5
6
Switch position indicator contacts OPEN / CLOSED
"Mechanical ON" pushbutton
"Mechanical OFF" pushbutton
Status indicator of spring energy store CHARGED / DISCHARGED
Manual lever for charging the spring energy store
Toggle
The following conditions must be met before the circuit breaker can be closed:
Circuit breaker in the OPEN position
Spring energy store compressed
Open command via remote access is not pending
Interlocking with open command is not pending (mechanical and electrical interlocks)