2.7.1 Portfolio of 3WL10 air circuit breakers
The 3WL10 air circuit breaker is part of the Siemens 3WL range, which covers all breaking
capacity classes between B and C and extends to 630 to 6300 A in the basic versions.
Class
+
6
1
&
I (440V) [kA]
cu
50004000320025002000160012501000800630 6300
%
-
66
55
-
42
85
66
55
-
-
100
80
66
130
-
100
-
-
150 3p
BG0 BG1 BG2 BG3 [A]
-
BG0
BG1
BG2
BG3
FS Frame size
Frame size and breaking capacity classes
The 3WL10 air circuit breaker has size 0 and is suitable for:
Rated currents between 630 A and 1250 A
Rated voltages up to 690 V
Breaking capacity I
cu
of 42 kA, 55 kA, and 66 kA at 440 V AC
Selective response
With its contact system, the 3WL10 air circuit breaker is designed for time-selective time-delayed
tripping.
A short-circuit-induced trip can be delayed for up to 400 ms (short-time-delayed short-circuit
protection ST).
Between these, you have extensive possibilities for 󹪝ne adjustment of the values, in respect
of current response thresholds, delay times and for switching between characteristics, such
as 󹪝xed delay time and inverse-time I²t characteristic
For maximum requirements, the instantaneous short-circuit protection (INST) can
additionally be disabled to temporarily deactivate or increase the current response threshold
of the short-circuit protection ST up to the I
cw
value of the device. After this utilizable time and
current limit has been exceeded, the circuit breaker instantaneously trips within 10 ms and
interrupts the overcurrent within 30 ms.
These settings give downstream devices time to clear the fault in the feeder a󹪜ected (time-
selective response, thus ensuring maximum availability in the outgoing feeders).
On the other hand, a system can be protected speci󹪝cally by optimization of the circuit
breaker for fast response. In this case, it clears a lower-level fault within 30 ms, irrespective
of any selective response.
Description
2.7Possible uses and portfolio
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
24 Equipment Manual, 10/2023, L1V30499596002-03