5.2 Mounting and connecting the device
5.2.1 Tightening torques at a glance
Connection technology Tightening torque
Connection
Connection methods -
Circuit breakers
[Nm]
Connection
Connection method -
Cables and busbars
1)
[Nm]
Connections of the xed-mounted breaker version
Horizontally / vertically ori‐
entable
rear connections
20
40
Front
terminals for main circuit
connection
18 18
Front connection bars, ex‐
tended
18 40
Front connection bars,
broadened
18 40
Copper/aluminum cable
connection bar
18
Connections of the guide frame
Horizontally / vertically ori‐
entable
rear connections
20
40
Front
terminals for main circuit
connection
12 40
Front connection bars, ex‐
tended
12 40
Front connection bars,
broadened
40 40
Copper/aluminum cable
connection bar
40
1)
You will nd the dimensions for the diagrams in Chapter Power supply, grounding, and
connection (Page140).
Connection and commissioning
5.2Mounting and connecting the device
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
154 Equipment Manual, 10/2023, L1V30499596002-03