The operating value is described as factor >1 of the line frequency - settable to 50Hz or
60Hz.
In this way, the distribution board can be protected from impermissible deviations in the line
frequency.
Undervoltage protection (V
u
)
The undervoltage protection responds with a denable denite-time delayt
u
(U) as soon as a
phase-to-phase voltage (U
ph
-U
ph
) falls below the operating valueU
u
.
The operating value is described as factor <1 of the rated voltage U
n
of the power system.
The rated voltage U
n
can be variably set from 100V to 690V.
In this way, the distribution board can be protected from impermissible deviations in the line
voltage.
Overvoltage protection (V
o
)
The overvoltage protection responds with a denable denite-time delayt
o
(U) as soon as a
phase-to-phase voltage(U
ph
-U
ph
) rises above the operating valueU
o
.
The operating value is described as factor >1 of the rated voltage U
n
of the power system.
The rated voltage U
n
can be variably set from 100V to 690V.
In this way, the distribution board can be protected from impermissible deviations in the line
voltage.
2.9.4.1 Characteristic curves
The settings selected for the trip unit of a circuit breaker depend on the technical environment
(e.g. switchboard and applications) and the type of equipment to be protected. It is the
responsibility of the system planner to calculate and dimension the protection settings in
accordance with the valid rules.
The following diagram shows the tripping characteristics of the circuit breaker.
Description
2.9Electronic trip unit ETU
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
60 Equipment Manual, 10/2023, L1V30499596002-03