5.2.2 Mounting connections
The rear terminals, horizontally and vertically oriented, are con󹪝gured in the factory both on the
󹪝xed-mounted breaker version and on withdrawable breakers. All other connections are
mounted on these or di󹪜erent basic connections (e.g. front terminal for main circuit connection
for the 󹪝xed-mounted breaker, 󹪞ange for the withdrawable breaker). The circuit breaker is
delivered to the user with the connections chosen in the basic con󹪝guration of the circuit
breaker. Any necessary installation of connections is described below.
Mounting front extended terminals for main circuit connection and circular conductor terminals
4x240 mm²
Front extended terminals for main circuit connection and circular conductor terminals are
supplied unmounted with the circuit breaker.
Screw the front extended terminals for main circuit connection or circular conductor
terminals to the front terminals for main circuit connection.
Note the operating instructions of the relevant connection system (see Chapter Product-
speci󹪝c information (Page9)).
Connection and commissioning
5.2Mounting and connecting the device
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Equipment Manual, 10/2023, L1V30499596002-03 155