Z option choice of communications module
With this Z option, the communications module for the 󹪝rst slot is de󹪝ned.
A second communications module with a further Z option can additionally be selected from
the list. This module then occupies a further slot that is no longer available for other modules.
PROFIBUS module COM040: F02
PROFINET module COM041: F03
Modbus TCP module COM043: F11
Modbus RTU module COM042: F12
Digital I/O module IOM040: K56
Example article number, a PROFINET module COM41:
3 W L 1 0 1 0 - 2 C F 4 1 - 1 L B 1 - Z L08 + F03
Z option digital signaling switch
As standard, every ETU is delivered with a ready-to-close signaling switch (RTC) with four
auxiliary switches AUX4CO and one trip alarm switch (S24) with a standard contact. These
accessories can optionally also be ordered with digital and mixed contacts. You will 󹪝nd
more information in the catalogs for 3WL10 and 3VA27 (see Chapter Reference documents
(Page10)).
For the withdrawable breaker, the position signaling switch 400 V AC is delivered as standard
with the guide frame. The guide frame signaling switch can also be ordered optionally with
digital contacts.
The spring charge signaling switch (S21) is delivered with standard contacts. It can optionally
be replaced by the version with a contact for the digital signal.
In the catalogs for 3WL10 and 3VA27, you will also 󹪝nd information on the con󹪝gurable locks
and interlocking methods.
Compilation of the article number has been completed. The individually con󹪝gured circuit
breaker can now be ordered with it.
A.2 Menu structure of the ETUs of the 6-series
Legend
The legend explains the ETU menu options.
Entry Description
parameter [MIN...MAX] Parameters that can be set within a de󹪝ned range
O󹪜, On Submenu in which one of the entries must be selected
current value The current measured value is displayed
Appendix
A.2Menu structure of the ETUs of the 6-series
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
254 Equipment Manual, 10/2023, L1V30499596002-03