7.5 Basic unit and accessories
7.5.1 Removing the front plate and accessories
For further maintenance, the circuit breaker must be partially disassembled:
1. Remove the front plates and terminal covers, see Chapter Installing accessories (Page167).
2. Remove the spring charging motor MO (Page174), if installed.
3. Remove the undervoltage release UVR (Page174), if installed.
4. Discharge the springs of the tripping mechanism.
5. Remove the cover over the mechanical pushbuttons.
Service and maintenance
7.5Basic unit and accessories
3VA27 molded case circuit breakers & 3WL10 air circuit breakers