Ambient temperature
The circuit breaker can be operated in ambient temperatures from -25 °C to +70 °C. At
temperatures of up to +70 °C, too, the rated current is not reduced (derating, see below).
The display of the electronic trip units of the 6-series is active over the entire operating range.
The permissible storage temperature in original Siemens packaging is between -40 °C
and+70 °C.
Installation altitudes
An installation altitude above 2000 m can result in higher temperatures on the switching
devices. The lower density of air can signicantly reduce heat dissipation. The arcing
behavior and the conductivity of the density-dependent ionized gas mixture are also less
favorable at greater altitudes. This makes it necessary to decrease rated operational voltage
and the rated uninterrupted current.
Altitude [m] 2000 3000 4000 5000
Rated voltage 440V [V] 440 387 343 300
Rated voltage 690V [V] 690 607 538 470
Rated uninterrupted current [%I
n
] 100 98 93 90
Rated ultimate short-circuit
breaking capacity ACI
cu
[%I
cu
@U
e
]
100 100 100 100
See also
Installation in the switchboard (Page138)
4.1.5 Current reduction
4.1.5.1 Current reduction depending on the ambient temperature on the 3WL10
The circuit breaker itself has no derating within the application temperatures.
Current
rating I
n
[A]
Ambient temperature
< 40 °C 45 °C 50 °C 55 °C 60 °C 65 °C 70 °C
630 100% 100% 100% 100% 100% 100% 100%
800 100% 100% 100% 100% 100% 100% 100%
1000 100% 100% 100% 100% 100% 100% 100%
1250 100% 100% 100% 100% 100% 100% 100%
Application planning
4.1Types of installation and installation locations
3VA27 molded case circuit breakers & 3WL10 air circuit breakers