3.2 Electromechanical accessories
3.2.1 Auxiliary releases for 3VA27 / 3WL10
Closing coil (CC) (for breaker with stored energy operating mechanism only)
Undervoltage release (UVR) / shunt release (ST2)
Shunt release (ST)
Undervoltage release (UVR)
The undervoltage release trips the circuit breaker if the rated control supply voltage U
s
fails or
drops to between 70% and 35% of its normal value (in compliance with the relevant standard).
The undervoltage release can be used for:
Safe remote-controlled tripping
Interlocking during closure
Checking the voltage in the primary and secondary circuits
The undervoltage release is powered via the auxiliary conductor terminal system.
Note
The circuit breaker can be reclosed at a coil supply voltage of 85% to 110%U
n
.
Accessories
3.2Electromechanical accessories
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
94 Equipment Manual, 10/2023, L1V30499596002-03