3.4.2 Front mounted rotary operator
The front mounted rotary operator with door interlock is a rotary operator that is located directly
on the circuit breaker and can be installed both in the control cabinet and through the control
cabinet door. The front mounted rotary operator locks the door automatically when it is turned
to position ON.
The door sealing frame is contained in the scope of delivery of the front mounted rotary
operator.
Device for mounting a cylinder lock
Device for up to 3 padlocks
Defeat function of the door interlock
Handle with device for up to 3padlocks
Door interlock
The door interlock of the door mounted rotary operator locks the door as soon as the door
mounted rotary operator is turned to position ON.
The door interlock can be overridden by a deliberate action. This is done by pressing the
door interlocking pin on the left side of the masking plate with a sharp object (e.g. a narrow
screwdriver). This means that the door can be opened with the operator in position ON so
that maintenance can be carried out, for example.
Accessories
3.4Rotary operators
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Equipment Manual, 10/2023, L1V30499596002-03 111