Vertical Horizontal
right
Horizontal
left
Vertical -
rotated 180°
Ceiling
mounting
Floor mount‐
ing
Wall mounting
Fixed-mounted breaker ✓ ✓ ✓ - ✓ ✓
Withdrawable breaker ✓ ✓ ✓ -
With front mounted ro‐
tary operator
✓ ✓ ✓ - ✓ ✓
With door mounted ro‐
tary operator
✓ ✓ ✓ - ✓ ✓
Floor mounting ✓ N.A. N.A. - N.A. N.A.
Wall mounting ✓ ✓ ✓ - ✓ ✓
Interlocks
(mechanical, direct, ca‐
ble, ...)
✓ ✓ ✓ - ✓ ✓
3VA27 molded case circuit breaker - with stored energy operating mechanism
Fixed mounting incl.
spring charging motor
✓ ✓ ✓ - - -
Withdrawable breaker ✓ ✓ ✓ - - -
Floor mounting ✓ N.A. N.A. N.A. N.A. N.A.
Wall mounting ✓ ✓ ✓ - - -
Interlocks (mechanical,
direct, cable, ...)
✓ ✓ ✓ - - -
Note
To integrate the circuit breaker optimally into the control panel, the 4-pole circuit breaker can
optionally be ordered with the neutral pole on the right or left-hand side of the circuit breaker.
These are basic versions of the circuit breaker and are permanently dened in the circuit breaker.
In all these versions, the circuit breaker is capable of full performance (no derating, full current
carrying capacity, and protection settings).
Phase sequence neutral left: N - L1 - L2 - L3
Phase sequence neutral right: L1 - L2 - L3 - N
The phase sequence L1, L2, L3 can be subsequently changed (to L3, L2, L1) by the user in the
electronic trip units of the 6-series to match any system conguration.
Mounting options
In addition to oor mounting, both the xed-mounted breaker and the withdrawable breaker
permit direct rear wall mounting.
For oor mounting of the xed-mounted breaker version, mounting supports are required
(see Section Support for oor xation (xed breaker) (Page123)).
Application planning
4.1Types of installation and installation locations
3VA27 molded case circuit breakers & 3WL10 air circuit breakers