&RPSDUWPHQW
&RPSDUWPHQW



3WL10
1 circuit breaker per panel width section in the switchboard
&RPSDUWPHQW
&RPSDUWPHQW



Circuit breaker power with rear terminals for main circuit con‐
nection
Horizontally oriented Vertically oriented
I
u
[A]
Busbar
connection
[mm]
Com‐
part‐
ment
Ambient temperature Ambient temperature
35 °C 45 °C 55 °C 35 °C 45 °C 55 °C
630 2 x 40 x 5 2 630 A 630 A 630 A 630 A 630 A 630 A
800 2 x 50 x 5 2 800 A 800 A 800 A 800 A 800 A 800 A
1000 2 x 50 x 10 /
2 x 50 x 8
1)
2 1000 A 1000 A 1000 A 1000A 1000A 1000A
1250 2 x 50 x 10 /
2 x 50 x 8
1)
2 1250A 1250A 1200A 1250A 1250A 1250A
1)
Horizontally oriented: 2 x 50 x 10 mm / vertically oriented: 2 x 50 x 8 mm
Application planning
4.1Types of installation and installation locations
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Equipment Manual, 10/2023, L1V30499596002-03 139

Table of Contents