I
n
[A] [mm] Horizontal front terminals Vertical front terminals
1000
2 x 50 x 10 ✓ —
2 x 50 x 8 — ✓
1250 2 x 50 x 10 ✓ —
2 x 50 x 8 — ✓
1600
(3VA27)
2 x 50 x 10 ✓ —
2 x 50 x 8 — ✓
W
min
mm
[in]
W
max
mm
[in]
n D
max
mm
[in]
∅
mm
[in]
H
mm
[in]
*
Nm
[lb-in]
Vertically orientable
rear terminals
— 24
[0.95]
1 … 4 — 11
[0.43]
12.5
[0.49]
40
[354]
Horizontally orientable
rear terminals
— 24
[0.95]
1 … 4 — 11
[0.43]
12.5
[0.49]
40
[354]
Front
terminals for main circuit
connection
— 24
[0.95]
1 … 2 20
[0.79]
11
[0.43]
14
[0.55]
18
[159.3]
Front connection bars, ex‐
tended
— 50
[1.97]
1 … 2 — 11
[0.43]
— 40
[354]
— 24
[0.95]
1 … 4
Front connection bars,
broadened
— 22
[0.86]
1 x 3
1 x 2
— 13
[0.5]
— 40
[354]
44
[1.73]
1 … 4
* Tightening torque
Application planning
4.2Power supply, grounding, and connection
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Equipment Manual, 10/2023, L1V30499596002-03 143