W
min
mm
[in]
W
max
mm
[in]
n D
max
mm
[in]
mm
[in]
H
mm
[in]
*
Nm
[lb-in]
Vertically orientable rear
terminals for main circuit
connection
:
T
+
24
[0.95]
1 … 4 11
[0.43]
12.5
[0.49]
40
[354]
Horizontally orientable rear
terminals for main circuit
connection
24
[0.95]
1 … 4 11
[0.43]
12.5
[0.49]
40
[354]
Copper/aluminum cable
connection bar
35
[1.37]
1 … 6 14.5
[0.57]
17.5
[0.69]
40
[354]
Front extended
terminals
50
[1.97]
1 … 2 11
[0.43]
12.5
[0.49]
40
[354]
24
[0.95]
1 … 4
Front connection bars,
broadened
22
[0.86]
1 x 3
1 x 2
13
[0.5]
40
[354]
44
[1.73]
1 … 4
* Tightening torque
See also
Accessories for connection and insulation (Page87)
Grounding
The 󹪝xed-mounted circuit breaker does not require grounding.
Application planning
4.2Power supply, grounding, and connection
3VA27 molded case circuit breakers & 3WL10 air circuit breakers