EasyManua.ls Logo

Siemens SENTRON 3WL10 - Page 188

Siemens SENTRON 3WL10
272 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setting the line frequency with the DIP switches
1. Set the DIP switches in the "Hz" area to the correct line frequency.
Example line frequency 50 Hz:
Hz
60
50
Entering parameters on the electronic trip units of the 6-series
The parameters of each protection release are entered with the control keys of the ETU to the
right of the display. You will 󹪝nd information on the control keys and the menu structure in
Chapter Design of the electronic trip units (Page48).
Entering parameters
1. Use the arrow keys to navigate to the parameter display.
2. Press the OK control key.
Parameter editing mode is active. The default setting for the PIN is "00001".
3. Use the arrow keys to navigate to the parameter area of the required protection release.
4. Press the control key OK.
The parameter can now be set or modi󹪝ed.
5. Use the arrow keys to set the parameter and con󹪝rm the value with the control key OK.
The newly set parameter value is now active.
6. With the control key HOME, go back to the start screen.
Note
Deactivating the password
Entering PIN "00000" deactivates the password.
Operation
6.1Operation
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Equipment Manual, 10/2023, L1V30499596002-03 187

Table of Contents

Other manuals for Siemens SENTRON 3WL10

Related product manuals