Main components of the guide frame
Mounting location of connection technology
Racking handle
Pushbutton for unlocking racking (Push before Operating, to rack the circuit breaker positions
using the racking handle)
Hole for inserting the racking handle
Circuit breaker position indicator
Racking rail
Lower shutter
Upper shutter
Locking lever
Circuit breaker positions in the guide frame
Using the racking handle, the circuit breaker can be put in three di󹪜erent positions in the guide
frame:
CONNECT:
The circuit breaker is connected to the main circuit. The auxiliary circuits are also closed.
TEST:
In the TEST position, the main contacts of the circuit breaker are not connected to the main
circuit, only to the auxiliary circuit. This allows the functionality of the auxiliary circuit and all
of its components (auxiliary switches, auxiliary releases, communication, etc.) to be tested
when the main circuit is open.
DISCON:
The circuit breaker is not connected to the main circuit nor to the auxiliary circuit. In the
DISCON (DISCONNECT) position, it can be removed from the guide frame.
The circuit breaker position is indicated below the hole for inserting the racking handle.
Description
2.8Basic unit
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Equipment Manual, 10/2023, L1V30499596002-03 33