Parameter Value range Default Re-parame‐
terization in
RUN
Eciency range
HART activated (Page 31)
• deactivated
• activated
Can only be congured when the
"HART gate" is activated and the
measuring range "4..20mA" is
set.
deactivated No
Channel
Number HART message
frame repetitions
(Page 28)
0 to 10
Only relevant when the "HART ac‐
tivated" parameter is activated.
5 No Channel
Diagnostics HART
(Page 32)
• deactivated
• activated
Only relevant when the "HART ac‐
tivated" parameter is activated.
activated No Channel
Module parameters
Diagnostics: missing pow‐
er supply voltage L+
(Page 29)
Activated (display only) activated No Module
Behavior after channel
fault (Page 34)
• Passivate the entire module
• Passivate channel
Passivate channel No Module
HART gate (Page 30)
• O
• On
O No
Module
Interference frequency
suppression (Page 34)
• 60 Hz
(integration time 16.6 ms)
• 50 Hz
(integration time 20 ms)
When 50 Hz is set, the 400 Hz in‐
terfering signals are also ltered
automatically.
50 Hz No Module
Channel n
Measurement type
(Page 31)
• deactivated
• 2‑wire
• 4‑wire
2‑wire No Channel
Measuring range
(Page 31)
• 0..20mA
• 4..20mA
4..20mA No Channel
Smoothing (Page 29)
• 1 (none)
• 4
• 16
• 64
1 No Channel
Diagnostics wire break
(Page 32)
• deactivated
• activated
activated No Channel
Parameters/address space
5.3 Module/channel parameters
F-AI 8xI 2-/4-wire HART HA
24 Equipment Manual, 09/2021, A5E50557845-AA