Parameter Value range Default Re-parame‐
terization in
RUN
E󹪟ciency range
HART activated (Page 31)
deactivated
activated
Can only be con󹪝gured when the
"HART gate" is activated and the
measuring range "4..20mA" is
set.
deactivated No
Channel
Number HART message
frame repetitions
(Page 28)
0 to 10
Only relevant when the "HART ac‐
tivated" parameter is activated.
5 No Channel
Diagnostics HART
(Page 32)
deactivated
activated
Only relevant when the "HART ac‐
tivated" parameter is activated.
activated No Channel
Module parameters
Diagnostics: missing pow‐
er supply voltage L+
(Page 29)
Activated (display only) activated No Module
Behavior after channel
fault (Page 34)
Passivate the entire module
Passivate channel
Passivate channel No Module
HART gate (Page 30)
O󹪜
On
O󹪜 No
Module
Interference frequency
suppression (Page 34)
60 Hz
(integration time 16.6 ms)
50 Hz
(integration time 20 ms)
When 50 Hz is set, the 400 Hz in‐
terfering signals are also 󹪝ltered
automatically.
50 Hz No Module
Channel n
Measurement type
(Page 31)
deactivated
2‑wire
4‑wire
2‑wire No Channel
Measuring range
(Page 31)
0..20mA
4..20mA
4..20mA No Channel
Smoothing (Page 29)
1 (none)
4
16
64
1 No Channel
Diagnostics wire break
(Page 32)
deactivated
activated
activated No Channel
Parameters/address space
5.3 Module/channel parameters
F-AI 8xI 2-/4-wire HART HA
24 Equipment Manual, 09/2021, A5E50557845-AA