Parameter Value range Default Re-parame‐
terization in
RUN
E󹪟ciency range
HART activated (Page 31)
deactivated
activated
Can only be con󹪝gured when the
"HART gate" is activated and the
measuring range "4..20mA" is set.
deactivated No
Channel
Number HART message
frame repetitions
(Page 28)
0 to 10
Only relevant when the "HART ac‐
tivated" parameter is activated.
5 No Channel
Diagnostics HART
(Page 32)
deactivated
activated
Only relevant when the "HART ac‐
tivated" parameter is activated.
activated No Channel
Terminal block
Double-width terminal
block (Page 29)
no
yes
No No Module
Potential group
Potential group (Page 33)
Potential group of the left
module (dark gray terminal
block)
New potential group (light
gray terminal block)
No potential group (black ter‐
minal block)
New potential group
(light gray terminal
block)
No Module
a
The F_source_address is automatically preset with the value "1" in S7 F/FH Systems and cannot
be changed in the properties of the I/O module.
b
The F_destination_address is automatically preset uniquely station-wide.
Note
Unused channels
"Disable" unused channels in the parameter assignment to improve the cycle time of the
module.
You can 󹪝nd more information on this in the section "Response times (Page 113)".
A deactivated channel always returns the analog value 0x0000 and QI = 0 ("Substitute value is
output").
Parameters/address space
5.3 Module/channel parameters
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA 25