Article number 6DL1161-6BH00-0PH1
• between the channels and the power supply
of the electronics
No
Isolation
Isolation tested with 1 500 V DC/1 min, type test
Ambient conditions
Ambient temperature during operation
• horizontal installation, min.
-40°C
• horizontal installation, max.
70°C
• vertical installation, min.
-40°C
• vertical installation, max.
60°C
Dimensions
Width 22.5mm
Height 115mm
Depth 138mm
Weights
Weight, approx. 135g
Derating curve
The following gure shows the load current derating with horizontal and vertical mounting
positions.
Total current I / A
Total current I / A
Vertical mounting
position
Horizontal mounting
position
Load current in A
Temperature in °C
3.00
2.50
2.00
1.50
1.00
0.50
0.00
0-40 -20 20 40 60 80
Cycle time
The cycle time describes the time slice in which signals from the inputs are acquired and
processed. The cycle time of the I/O module is 1ms (250μs for time stamping).
Minimum pulse length
In order for a pulse or an edge transition to be reliably detected by the I/O module, the signal
status must be active for at least the duration of the minimum pulse length.
In non-redundant mode, the minimum pulse length is greater than the input delay and
greater than the cycle time.
Technical specications
DI 16x24VDC PA
34 Equipment Manual, 06/2023, A5E51654101-AA