IM151-1 FO STANDARD interface module (6ES7151-1AB05-0AB0)
Manual, 02/2010, A5E01075965-03
11
Parameters
2
2.1 Parameters for the IM151-1 FO STANDARD interface module
Parameterize register
Table 2- 1 Parameters for the IM151-1 FO STANDARD interface module
IM151-1 FO STANDARD Value range Default setting
5
Applicability
DP interrupt mode DPV0/DPV1 DPV0 ET 200S
Bus length ≤ 1 m / > 1 m ≤ 1 m ET 200S
Operation at set < > actual
configuration
1
disable/enable Disable ET 200S
Diagnostic interrupt
3
disable/enable Disable ET 200S
Process interrupt
3
disable/enable Disable ET 200S
Remove/insert module
interrupt
2 3
disable/enable Disable ET 200S
Identifier-related diagnostic data disable/enable Enable ET 200S
Module status disable/enable Enable ET 200S
Channel-specific diagnostics disable/enable Enable ET 200S
Option handling in general disable/enable Disable ET 200S
Option handling with / without reserve
module
with reserve module ET 200S
Option handling:
Slots 2 to 63
disable/enable Disable ET 200S
Analog value format
4
SIMATIC S7/
SIMATIC S5
S7 ET 200S
Interference frequency
suppression
50 Hz / 60 Hz 50 Hz ET 200S
Reference junction slot None /2 to 63 None ET 200S
Reference junction input RTD on channel 0/
RTD on channel 1
0 ET 200S
1
See also the "option handling" parameter.
2
The default setting of the parameter in the GSD file is "disable".
3
Only parameterizable in DPV1 operation.
4
The parameter only exists when configuring via the GSD file.
5
The default settings apply to the default startup (if no other parameters have been assigned by the
DP master).