Functions
3.1 Option handling with RESERVE modules
IM151-1 FO STANDARD interface module (6ES7151-1AB05-0AB0)
Manual, 02/2010, A5E01075965-03
19
Substitute values
If you have assigned an electronic module for the RESERVE module, the following substitute
values are signaled:
Digital input modules: 0
Analog input modules: 7FFF
H
Function module: 0
See also
Option handling in general (Page 12)
3.1.5 Controlling and monitoring options with RESERVE modules
Introduction
You can use the control interface (PIQ) and feedback interface (PII) to control and monitor
options by means of the user program.
Recommendation: Before working with the ET 200S optional enhancements, check whether
all the configured electronic modules are plugged in using the feedback interface (refer to the
table below).
Note
SFCs 14/15 can be used to consistently access the control and feedback interface.
Principle
The control and feedback interface is located in the input and output process image of the
PM-E DC24..48V, PM-E DC24..48V/AC24..230V and PM-E DC24V HF power modules. It
can only be accessed if entries ending in ...O or ...SO for that power module were selected in
the configuration software.
One bit is available for each ET 200S electronic or RESERVE module slot.
Control interface: Slot 2 to 63
Feedback interface: Slot 1 to 63
     



       

       
      
      
      
      
(%$%[
(%$%[
(%$%[
(%$%[
(%$%[
(%$%[
(%$%[
(%$%[
Figure 3-3 Control (PIQ) and feedback interface (PII)
(*) irrelevant