Functions
3.1 Option handling with RESERVE modules
IM151-1 FO STANDARD interface module (6ES7151-1AB05-0AB0)
18 Manual, 02/2010, A5E01075965-03
3.1.4 Assigning parameters for option handling with RESERVE modules
Introduction
In
STEP 7
or
COM PROFIBUS
you assign the parameters for the electronic modules which
you want to use in future applications, e.g. 4DI H, on the RESERVE module slots (or the
expansion modules on the right-hand end of the station):
Drag the electronic module to the configuration table
Assign the parameters
Procedure
1. Drag a PM-E 24..48 VDC or PM-E 24..48 VDC/24..230 VAC power module with one of
the following entries into the configuration table:
...O (option handling) or
...SO (status byte + option handling)
Note
Entry of the power module with the ending ...O or ...SO can only be made once in the
ET 200S configuration!
2. Assign parameters to the interface module as follows:
Interface module Parameter Setting Description
Option handling,
general
enable Option handling is activated for
the entire ET 200S.
Option handling:
Slots 2 to 63
Enable (all the slots
where RESERVE
modules can be located)
There are RESERVE modules
or a configured electronic
module on the slot. A diagnostic
is not signaled.
IM151-1
STANDARD
or
IM151-1 FO
STANDARD
or
IM151-1 HIGH
FEATURE
Option handling:
With/without
RESERVE modules
With RESERVE
modules
Selects option handling with
RESERVE modules
Note
If "Operation for set < > actual installation" is blocked for parameter assignment,
the ET 200S does not start up if a module is missing or if an incorrect module is plugged
in. The diagnostic "No module" or "Incorrect module" is signaled.
The ET 200S starts up if you enable option handling for the slot where a RESERVE
module is plugged in. A diagnostic is not signaled.