Error and system messages
4.4 Diagnostics with STEP 7
IM151-1 FO STANDARD interface module (6ES7151-1AB05-0AB0)
42 Manual, 02/2010, A5E01075965-03
Note
The length of the diagnostics frame varies depending on the parameter assignment:
Between 6 and 62 bytes in DPV0 mode
Between 6 and 110 bytes in DPV1 mode
You can identify the length of the last received diagnostics frame in
STEP 7
by referring to
the RET_VAL parameter of the SFC 13.
4.4.3 Station statuses 1 to 3
Definition
Station statuses 1 to 3 provide an overview of the status of a DP slave.
Structure of station status 1 (byte 0)
Table 4- 3 Structure of station status 1 (byte 0)
Bit Meaning Cause/Remedy
0 1: The DP slave cannot be accessed by the DP
master.
Is the correct PROFIBUS address set on the DP slave?
Is the bus connector plugged in?
Is the DP slave connected to the voltage supply?
Is the RS-485 repeater set correctly?
Has the DP slave been reset?
1 1: The DP slave is not yet ready to exchange data.
Wait, the DP slave is currently starting up.
2 1: The configuration data transferred from the DP
master to the DP slave does not match the slave
configuration.
Has the correct station type or the correct DP slave
configuration been entered in the configuration software?
3 1: External diagnostics information is pending.
(Group diagnostics display)
Evaluate the ID-specific diagnostics information, the
module status, and/or the channel-specific diagnostics
information. As soon as all errors have been eliminated,
bit 3 will be reset. The bit will be set again when there is a
new diagnostics message in the bytes of the
aforementioned diagnostics.
4 1: The required function is not supported by the DP
slave (for example, changing the PROFIBUS
address by means of software).
Check the configuration.
5 1: The DP master cannot interpret the response of
the DP slave.
Check the bus configuration.
6 1: The DP slave type does not match the software
configuration.
Has the correct station type been entered in the
configuration software?
7 1: Parameters have been assigned to the DP slave
by a different DP master (not the one that currently
has access to the DP slave).
The bit is always 1, for example, if you access the DP
slave with the programming device or another DP master.
The PROFIBUS address of the DP master that assigned
parameters to the DP slave is located in the "Master
PROFIBUS address" diagnostics byte.