Functions 
  3.1 Option handling with RESERVE modules 
IM151-1 FO STANDARD interface module (6ES7151-1AB05-0AB0) 
Manual, 02/2010, A5E01075965-03 
21 
3.1.6  Troubleshooting for option handling with RESERVE modules 
Troubleshooting for option handling 
Table 3- 3  Troubleshooting option handling 
Event  Cause  Action 
There are multiple entries in the 
ET 200S configuration for power 
modules ending in ...O or ...SO. 
Check and correct the 
configuration in HW Config. 
ET 200S does not start up; 
configuration error 
There are no entries of power 
modules ending in ...O or ...SO 
in the ET 200S configuration.  
Use a power module entry 
ending in ...O or ...SO in HW 
Config. 
3.1.7  Address area for option handling and status byte with RESERVE modules 
Address area for option handling and status byte 
You can control and monitor option handling and evaluate the status byte of the power 
module using the control (PIQ) and feedback (PII) interface. 
The address range in the control (PIQ) and feedback interface (PII) depends on the 
configuration, i.e. the selection of the corresponding entry in the configuration software.  
This table shows the PII feedback interface and the PIQ control interface for various entries.  
Table 3- 4  PII feedback interface and PIQ control interface 
In STEP 7/HW Config or 
COM PROFIBUS or other 
configuration software 
Feedback interface PII  Control interface PIQ 
Usual entry for the power 
module 
---  --- 
Ends in ...S  Ibx  Status byte  --- 
Ends in ...O  IBx 
... 
IBx+7 
 
Option handling 
OBx 
... 
OBx+7 
 
Option handling 
EBx 
... 
EBx+7 
 
Option handling 
ABx 
... 
ABx+7 
 
Option handling 
Ends in ...SO 
IBx+8  Status byte  OBx+8  Not applicable